Setting Procedure via Front Panel

for TS/TN-1500/3000 Series

Front Panel  
Function Setting Procedure
Step 1 The inverter should be turned off while resetting, input batteries should be connected. AC main can either be connected or disconnected, and the load
should be removed.
Step 2 Use an insulated stick to press the setting button and then turn on the
power switch. After pressing for 5 seconds, the inverter will send out a
“Beep” sound. User can release the button and go into the setting procedure.
First Level UPS and Energy Saving Mode Selection Step 3 Please refer to table below and check the LED status to see if the operating
mode is the one you need. (Factory setting: UPS mode)

Step 4 The LED will change state by pressing the setting button for 1 second and
then release.

Second Level Output Voltage and Frequency Adjustment Step 1 After selecting the operating mode, pressing the setting button for 3~5
seconds and the inverter will send out a “Beep” sound. The button can be
released and you can go on to the second section of “voltage / frequency”.
Step 2 Please refer to table below and check the LED status to see if the output
voltage / frequency is the one you need
(Factory setting: 230VAC/50Hz or 110VAC / 60Hz)

Step 3 The LED will change state by pressing the setting button for 1 second and
then release.

Third Level Saving Mode Selection Step 1 After selecting the output voltage and frequency, press the setting button for 5 seconds and the inverter will send out a “Beep” sound. The button can be released and you can go into the setting section for “saving mode”.
Step 2 Please refer to table below and check the LED status. ( Factory setting: saving mode OFF )

Step 3 The LED will change state by pressing the setting button for 1 second and then release.
Step 4 Press the setting button for 5 seconds and the inverter will send out a “Beep” sound, the button can be released and all the setting are finished. The inverter will automatically store all the setting and then start to operate.